Water need special attention.
Leader Line Up :
- Check lights in M5
- Install DVD in M5
- Training Generator with BME Pak Marjiono at 10 o'clock
- Install grill decking room
- Will repaint the access point same as the wall color.
Work Activities :
Training Generator from Pak Marji BME :
Radiator
Must Change every 2 years
Recommended liquid Fleet guard coolant.
Formula 1 (fleet guard) 10 (Water)
For this Generator need 7 Gallon aqua for 1 generator.
Air Filter
Must Change every 5 years
clean every year
Oil Filter
Much Change every year or 250 running hours which one reach first
Batteries
Much Change every 2-3 years
Solar Tank
Must drain every month to clean the water from tank.
V-belt
Must Change 3-4 Years depend on the condition
Noisy Acceptable
100 DB inside area
70 DB outside area
Check Mansion 5 :
Pak Imam worker still coming to clean the roof dak from rubbish
Care team finishing in Pantry M5.
Tidak ada komentar: